Request Full DetailsPlace OrdersHome Product GuideContact UsDealer Opportunities

Magnum ultraviolet open channel water disinfection system











  What is ultraviolet? What is germicidal ultraviolet? What are the beneficial uses of germicidal ultraviolet?
What microorganisms are deactivated by ultraviolet? What are questions to ask when buying ultraviolet?
water disinfection systemuv lampswater disinfectionliquid uv disinfectioncommercial ultraviolet applications
Specification of Standard Magnum
ultraviolet open channel water disinfection system
Model Peak Flow
Rate
(GPM)
Peak Flow
Rate
(GPD)
Quantity
Of Lamps
Channel Size
"A"x"B"x"C"
(inches)
Transition Box
Size
"D"x"E"x"F"
Weir Box Size
"G"x"H"x"J"
(inches)
Inlet/Outlet
Flange Size 
"K"
Channel
Width
Effluent
Depth
HC2-64/2WC 69.4 100,000 4 96"x6"x15" 16"x14"x22" 20"x14"x22" 6" 6" 6"
HC2-64/3WC 104.2 150,000 6 96"x9"x15" 16"x16"x22" 20"x16"x22" 8" 9" 6"
HC2-64/4WC 138.9 200,000 8 96"x12"x15" 16"x16"x22" 20"x20"x22" 8" 12" 6"
HC2-64/5WC 173.6 250,000 10 96"x15"x15" 16"x22"x22" 20"x25"x22" 8" 15" 6"
HC2-64/6WC 208.3 300,000 12 96"x18"x15" 16"x22"x22" 20"x30"x22" 8" 18" 6"
HC2-64/7WC 243.0 350,000 14 96"x21"x15" 16"x28"x22" 20"x35"x22" 8" 21" 6"
1 Channel, Transition Box & Weir Box are Stainless Steel. 
2 Lamp Modules and Electronic Enclosure omitted for clarity. 
3 Flow rates are based on: 
- Maximum Total Suspended Solids (TSS) of 30mg/l
- Maximum Biological Oxygen Demand (BOD) of 30 mg/l 
- Minimum Ultraviolet Transmission of 65% per centimeter
4 Contact Authorized Distributor for further information
© copyright 2002 Atlantic Ultraviolet Corp
© copyright 2002 Atlantic Ultraviolet Corp
1
Ultraviolet system does not include concrete channels.
2 Lamp Modules and Electronic Enclosure omitted for clarity.
3 Flow rates are based on:
- Maximum Total Suspended Solids (TSS) of 30mg/l.
- Maximum Biological Oxygen Demand (BOD) of 30 mg/l.
- Minimum Ultraviolet Transmission of 65% per centimeter.
4 Contact Authorized Distributor for further information.
Model Peak Flow
Rate
(GPM)
Peak Flow
Rate
(GPM)
Peak Flow
(Cu. Meters/Day)
Quantity
Of Lamps
No. of
Modules
Channel
Width
Effluent
Depth
 HC4-64/4 277.7 400,000 1503 16 4 12" 12"
 HC4-64/5 347.2 500,000 1879 20 5 15" 12"
 HC4-64/6 416.6 650,000 2255 24 6 18" 12"
 HC4-64/7 486.1 700,000 2631 28 7 21" 12"
 HC4-64/8 555.5 800,000 3006 32 8 24" 12"
 HC4-64/9 625.0 900,000 3382 36 9 27" 12"
 HC4-64/10 694.4 1,000,000 3758 40 10 30" 12"


Safety Warnings and Instructions

Authorized Distributor of the Magnum Product Line
back to home & product directory